Taking The Contactor Truck Out Of The Panel - Siemens NXAIR Operating Instructions Manual

Air-insulated switchgear ≤ 17.5 kv / ≤ 40 ka / ≤ 4000 a busbar current
Hide thumbs Also See for NXAIR:
Table of Contents

Advertisement

Fig. 221: Turning the operating lever counter-
clockwise
Remove the operating lever.
To close the actuating opening, push the operating slide down as far as it will go.
Fit a padlock (optional) to the operating slide and close it.
The feeder is de-earthed.

13.16 Taking the contactor truck out of the panel

110-0134.9 / 14
Operating the contactor panel with panel width 435 mm
DANGER
Electric shock
The shutter mechanism of the busbar compartment is accessible when the
contactor truck has been moved away from the panel.
Padlock the busbar shutter mechanism immediately against actuation as
soon as the contactor truck was moved away from the panel.
As long as no contactor truck is in the panel, the shutter mechanism on
left side of the switching-device compartment must remain secured with
the padlock.
Do not remove the padlock at the shutter mechanism on the left side until
right before moving the contactor truck into the panel.
CAUTION
Injury
The mechanism inside the contactor truck can cause injuries by getting squeezed,
caught or cut.
Do not remove any parts of the covering.
NXAIR / ≤ 40 kA
Fig. 222: Position indicator in OPEN position
129

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents