Racking The Withdrawable Circuit-Breaker / Circuit-Breaker Truck To Service Position Manually - Siemens NXAIR Operating Instructions Manual

Air-insulated switchgear ≤ 17.5 kv / ≤ 40 ka / ≤ 4000 a busbar current
Hide thumbs Also See for NXAIR:
Table of Contents

Advertisement

Panels with motor operating mechanism control

27.7 Racking the withdrawable circuit-breaker / circuit-breaker truck to service position manually

394
NOTICE
Conflicting operation
The requirement of setting the panel to either local or remote control prevents
operating the panel locally and centrally at the same time.
For any local operations ─ manual or electrical ─ set the panel to local
control, for example by switching the local-remote switch to LOCAL
position.
NOTICE
Maloperation
Racking the withdrawable circuit-breaker / circuit-breaker truck is only permissible
if the circuit-breaker is in OPEN position.
Check if the circuit-breaker is in OPEN position.
If required, switch the circuit-breaker to OPEN position before racking.
NOTICE
Maloperation
Racking the withdrawable circuit-breaker / circuit-breaker truck is only permissible
if the feeder earthing switch is in OPEN position.
Check if the feeder earthing switch is in OPEN position.
If required, switch the feeder earthing switch to OPEN position before
racking.
NOTICE
Incorrect stress of the motor operating mechanism
When the withdrawable circuit-breaker / circuit-breaker truck is racked manually,
the motor operating mechanism is also turned via the wheel chain mechanism.
Turn the racking crank slowly and uniformly to avoid high reverse polarity
voltage.
NXAIR / ≤ 40 kA
110-0134.9 / 14