Siemens NXAIR Operating Instructions Manual page 385

Air-insulated switchgear ≤ 17.5 kv / ≤ 40 ka / ≤ 4000 a busbar current
Hide thumbs Also See for NXAIR:
Table of Contents

Advertisement

Several electrical interlocks support safe electrical operation:
Operating option
Racking the withdrawable
circuit-breaker / circuit-breaker
truck electrically
Opening / closing the circuit-
breaker electrically for testing
purposes
Opening / closing the circuit-
breaker electrically during
service
Opening / closing the feeder
earthing switch electrically for
testing purposes
Closing the feeder
earthing switch electrically
during service
110-0134.9 / 14
Panels with motor operating mechanism control
Preconditions for operating option
Low-voltage connector plugged
on
High-voltage door closed
Feeder earthing switch in OPEN
position
Circuit-breaker in OPEN position
Access released for
motor-operated racking
Control door closed
Low-voltage connector plugged
on
High-voltage door closed
Control door closed
Withdrawable circuit-breaker /
circuit-breaker truck
in test position
Low-voltage connector plugged
on
High-voltage door closed
Control door closed
Withdrawable circuit-breaker /
circuit-breaker truck
in service position
Low-voltage connector plugged
on
High-voltage door closed
Control door closed
Withdrawable circuit-breaker /
circuit-breaker truck
in test position
Low-voltage connector plugged
on
High-voltage door closed
Control door closed
Withdrawable circuit-breaker /
circuit-breaker truck
in service position
NXAIR / ≤ 40 kA
Electrical interlock
During an ongoing racking
procedure, racking in opposite
direction is interlocked
electrically.
During an ongoing racking
procedure, opening / closing the
circuit-breaker is interlocked
electrically.
During an ongoing racking
procedure, opening / closing the
feeder earthing switch
is interlocked electrically.
Opening / closing the circuit-
breaker electrically for testing
purposes is not interlocked
electrically.
Opening / closing the circuit-
breaker electrically during service
is not interlocked electrically.
Opening / closing the feeder
earthing switch electrically for
testing purposes is
not interlocked electrically.
Closing the feeder earthing switch
electrically during service is
interlocked electrically.
385