Siemens NXAIR Operating Instructions Manual page 183

Air-insulated switchgear ≤ 17.5 kv / ≤ 40 ka / ≤ 4000 a busbar current
Hide thumbs Also See for NXAIR:
Table of Contents

Advertisement

Preparations
The preparations for inserting the contactor truck include:
Verifying correspondence of truck type / version and panel type / version
Preparing the operating shaft for the feeder earthing switch
Verifying correspondence of truck type and panel type
To avoid inserting a truck into a panel not suitable for the truck type, verify that you have a
contactor truck at hand and that the present panel is a contactor panel.
To do so, carefully examine both the mimic diagram on the high-voltage door and the front
side of the truck.
Fig. 326: Mimic diagram on high-voltage
Verifying correspondence of truck version and panel version
To avoid inserting a contactor truck into a contactor panel not suitable for the truck type, verify
correspondence as regards (a) coding and (b) mechanical closing latch:
(a)
The contactor truck must have the same coding as the panel.
Carefully
the low-voltage connector with the pair of symbols on the top side of the contactor truck.
Fig. 328: Coding symbols on top side of low-
110-0134.9 / 14
Operating the contactor panel with panel width 600 mm
door of contactor panel
compare
the
pair
voltage connector
NXAIR / ≤ 40 kA
Fig. 327. Front side of contactor truck
of
coding
symbols
Fig. 329: Coding symbols on top side of
contactor truck
on
the
top
side
183
of