Interlocks; Mechanical Interlocks In Panel Versions With Withdrawable Parts - Siemens NXAIR Operating Instructions Manual

Air-insulated switchgear ≤ 17.5 kv / ≤ 40 ka / ≤ 4000 a busbar current
Hide thumbs Also See for NXAIR:
Table of Contents

Advertisement

7

Interlocks

7.1

Mechanical interlocks in panel versions with withdrawable parts

Action
Inserting the withdrawable part in the panel
Pulling the withdrawable part out of the panel
Racking the withdrawable part to
service position
Plugging on the low-voltage connector
Racking the withdrawable part to test position
Closing the circuit-breaker
Closing the circuit-breaker
Opening the circuit-breaker
Operating the feeder earthing switch
Operating the busbar earthing switch
Opening the high-voltage door
Closing the high-voltage door
110-0134.9 / 14
INFORMATION
Contactor panels with panel width 435 mm and 600 width mm are not available for
withdrawable switchgear.
NXAIR / ≤ 40 kA
Internal preconditions
Withdrawable part on the service truck
None
Withdrawable part inserted and interlocked
Low-voltage connector plugged on
High-voltage door closed
Circuit-breaker in OPEN position
Feeder earthing switch in OPEN position
Consistent coding between connector and
withdrawable part fulfilled
Circuit-breaker in OPEN position
Withdrawable part in interlocked end position
(test position or service position)
Undervoltage release not electrically operated
None
Withdrawable part in test position
None (see note given below)
Withdrawable part in test position
Low-voltage connector plugged on
Interlocks
29