9
UTILITY OPERATION

9.2.7 Operating System setting screen

Make the parameter setting (system setting) of the C Controller module.
Set the system-related parameters.
(1) System setting screen
System setting
Item
Points occupied by empty slot
Remote reset
9
- 42
9.2 C Controller Setting Utility
9.2.7 Operating System setting screen
POINT
1. In a multiple CPU system configuration, utilize the multiple CPU parameters
set to the QCPU (Q mode).
Utilizing the multiple CPU parameters prevents mismatches between the
settings of the C Controller module and those of each programmable
controller CPU.
2. When the multiple CPU parameters of the QCPU (Q mode) are not utilized in
a multiple CPU system configuration, complete the <<Multiple CPU setting>>
tab setting and then make the I/O assignment setting.
3. To update the settings into the C Controller module, write the parameters from
the <<Online operation>> tab and power off and then on or reset the C
Controller system.
Figure 9.39 System setting screen
Table9.22 Explanation of System setting screen
I/O assignment setting
Multiple CPU setting
Set the points for each empty slot of the main base unit and extension
base unit.
(Initial value: 16, Setting range: 0, 16, 32, 64, 128, 256, 512, 1024)
Select whether the remote reset of the C Controller module is enabled or
not. (Initial value: Not checked (Not enabled))
Communication diagnostics
Description
Reference
section
6.6.2
4.5.3
(To next page)