SETTINGS AND PROCEDURES BEFORE OPERATION
(2) When configuring a single CPU system
5
- 12
5.3 Settings and Procedures before Operation
Development environment (PC)
Figure 5.9 Single CPU system configuration
Procedures for operation
Start up the C Controller module.
On the C Controller setting utility, make system setting
necessary to use the C Controller module.
Perform I/O assignment of the main base unit and
extension base unit.
Perform the switch setting and detail setting of each
module.
Write the set parameters from the <<Online operation>>
tab of the C Controller setting utility to the C Controller
*1
module.
Reset the C Controller module with the RESET/SELECT
switch. (Resetting the module makes the written
parameters effective.)
Move the RUN/STOP/MODE switch of the C Controller
module from STOP to RUN, and check that the C
Controller module is in the RUN status (the RUN LED is
lit).
On the C Controller setting utility, check the operation
status (e.g. errors). (Module information, Event history,
Module monitor, system information, etc.)
No
Is there no error?
Create and debug a user program using Tornado, and
register it to the C Controller module.
Operation
* 1 To write the parameters, connect the utility to the C Controller module with the write
authority.(
Section 5.11, Section 9.1.3)
Figure 5.10 Flowchart for single CPU system configuration
C Controller module
Ethernet
Yes
This section (1)
Section 9.2.7
Section 9.2.8 (1)
Section 9.2.8 (2), (3)
Section 9.2.8 (2), (3)
Section 9.2.6
Section 5.4 (3)
Section 5.4 (2)
Section 9.2.2, 9.2.3,
9.2.5
Chapter 10