Mitsubishi MELSEC-Q Series User Manual page 605

C controller module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

18
TROUBLESHOOTING
Table18.8 Common error codes returned by bus interface functions and MELSEC data link functions (Continued)
Return value
(HEX)
-28663
Base number specification error
(0x9009)
The specified base number Is out of range.
-28664
Data transmission area occupied error
(0x9008)
-28665
No registration data error
(0x9007)
-28666
Data length error
(0x9006)
-28668
Reply data stored error
(0x9004)
-28669
Area number error
(0x9003)
The specified area number or offset address or mode is out of range.
-28671
Module identification error
(0x9001)
-28672
Processing code error
(0x9000)
(2) Error codes returned by bus interface functions
Return value
(HEX)
0
Normal completion
-201
Module identification error
(0xFF37)
The specified module identification is invalid.
-202
Path error
(0xFF36)
The specified path is invalid.
-203
Input number/output number error
(0xFF35)
The specified input number/output number is out of range.
-204
I/O Access size error
(0xFF34)
The specified I/O number + size is out of range.
-205
I/O number error
(0xFF33)
The specified I/O number is out of range.
-206
Program execution type error
(0xFF32)
The specified program execution type is out of range.
Offset error
-208
The specified offset is out of range.
(0xFF30)
The specified I/O number is AnS series module.
Buffer memory size error
-209
The specified offset + size is out of range.
(0xFF2F)
The address of specified data stored buffer pointer is 0.
-210
Read area size error
(0xFF2E)
The read area is too small.
Error description
* 1 In a single CPU configuration, reset the C Controller module.
In a multiple CPU configuration, reset CPU No.1.
The following provides the error descriptions and corrective actions corresponding to
individual error codes returned when the bus interface functions are executed.
Refer to this section (1) for the common error codes returned by bus interface
functions and MELSEC data link functions.
Table18.9 Error codes returned by bus interface functions
Error description
18.4.1 Actions by error codes generated at function execution
Check the specified base number.
Retry.
Reboot the system.
Reboot the system.
Demand once again.
Check the specified area number or offset
address or mode.
Check the parameter.
Check the specified module.
Reboot the system.
Install software package again.
Reboot the system.
Check the specified module identification.
Use the path pointer returned with
"QBF_Open".
Check the specified input number/output
number.
Check the specified I/O access size.
Check the I/O number + size.
Check the specified I/O number.
Check the specified program execution type.
Check the specified offset.
Check the specified I/O number.
Check the specified buffer memory size.
Check the offset + size.
Check the data stored buffer pointer.
Check the read size and read area size.
18.4 Error Code and Error Message Lists
Corrective action
*1
*1
*1
*1
Corrective action
(To next page)
18
- 45
17
18