9
UTILITY OPERATION

9.3 CC-Link utility

This section explains the operation of the CC-Link utility.
The following are the precautions for use of the CC-Link utility.
(1) Parameter details
Refer to the following manual for parameter details.
(2) Maximum number of concurrently applicable CC-Link utilities
Up to 8 CC-Link utilities can be activated and used at the same time.
(3) Precautions for writing parameters
Parameters written to the C Controller module become effective when the C
Controller module is powered off and then on or is reset.
(4) Precautions for connections from multiple CC-Link utilities to the same
C Controller module
Connection can be made from multiple CC-Link utilities to the same C Controller
module.
In this case, the CC-Link utilities may have different parameters.
To make all of the CC-Link utilities have the same parameters, read the parameters
from the C Controller module to each CC-Link utility.
(5) Tabs available in offline mode
When the connection status of the CC-Link utility is offline, only the items on the
<<Parameter setting>> and <<Target setting>> tabs can be set.
(6) Exiting Microsoft
Do not terminate Microsoft
Exit Microsoft
(7) Connection during script file execution
While script file processing is being executed (the RUN LED is flashing), access may
not be made from each utility to the C Controller module.
In such a case, connect each utility to the C Controller module after terminating the
script file processing.
Remark
CC-Link System Master/Local Module User's Manual
Windows
Windows
Windows
after terminating the CC-Link utility.
For the functions added to the CC-Link utility by version upgrade, refer to
Appendix 7.
while the CC-Link utility is running.
9.3 CC-Link utility
9
10
11
12
13
14
15
16
9
- 57

Advertisement

Table of Contents
loading

This manual is also suitable for:

Q06ccpu-v-h01

Table of Contents