Ex.
When the 17th error occurs:
The 17th error is stored in Error history No. 1, and the value 3600 (start address of Error history No. 1) is stored to Latest
address of error history.
'Latest address of error history'
(Un\G1): 3600
• Once the error history storage area becomes full, the existing data is overwritten in order, starting with 'Error
history No. 1' (Un\G3600 to Un\G3609), and error history logging continues. The overwritten history is
deleted.
• The same processing is performed for Alarm history when an alarm occurs.
• The stored error history is cleared when an analog output module is powered off or the CPU module is
reset.

Offset/gain initialization function

Offset/gain initialization
This function initializes the offset and gain values adjusted by the offset/gain setting to the factory defaults.
User range setting
User range setting (voltage)
User range setting (current)
1.
Set the mode to normal output.
2.
Set "D/A conversion not allowed (1)" in 'CH1 D/A conversion enable/disable setting' (Un\G500) to 'CH4 D/A conversion
enable/disable setting' (Un\G1100). Then, turn offonoff 'Operating condition setting request' (Un\G70, b9).
3.
Set "E20FH" to 'Offset/gain initialization enabled code' (Un\G305).
4.
Turn ON (1) 'Offset/gain initialization request' (Un\G70, b5).
After completion of the offset/gain initialization function, 'Offset/gain initialization enable code' (Un\G305) is initialized to
'0000H' and 'Offset/gain initialization completed flag' (Un\G69, b5) turns on (1).
2 FX5-4DA
236
2.4 Functions
Un\G3600
Error history 1
1st error
Un\G3610
Error history 2
2nd error
Un\G3620
Error history 3
3rd error
Un\G3750
Error history 16
16th error
Offset value
0 V
4 mA
Latest
17th error
Gain value
10 V
20 mA