■Enabling the setting
When 'Minimum value reset request' (Un\G109) turns offon, 'CH1 Minimum value' (Un\G101) is reset regardless of turning
offonoff of 'Operating condition setting request' (Un\G70, b9), and updated with the current value.
■Default value
The default value is off (0).
CH1 A/D conversion enable/disable setting
Set whether to enable or disable the A/D conversion.
For details on the A/D conversion enable/disable setting function, refer to the following.
Page 27 A/D conversion enable/disable setting function
Setting value
0
1
When a value other than the ones above is set, the setting is turned to A/D conversion disable (1).
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH A/D conversion enable/disable setting
CH A/D conversion enable/disable setting (in
FX3 allocation mode function)
■Enabling the setting
Turn offonoff 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■Default value
The default value is A/D conversion enable (0) for all channels.
CH1 Average processing specification
Select processing to be performed among the sampling processing, averaging processing, primary delay filter, and digital
filter.
Averaging processing consists of time average, count average, and moving average.
Setting value
0
1
2
3
4
5
Setting a value other than the above causes an averaging process specification setting range error (error code: 191H).
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Averaging process specification
CH Averaging process specification (In FX3
allocation mode function)
■Enabling the setting
Turn offonoff 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■Default value
The default value is Sampling processing (0) for all channels.
Setting content
A/D conversion enable
A/D conversion disable
CH1
CH2
500
700
1321
1322
Setting content
Sampling processing
Time average
Count average
Moving average
Primary delay filter
Digital filter
CH1
CH2
501
701
1081
1082
CH3
CH4
900
1100
1323
1324
CH3
CH4
901
1101
1083
1084
Appendix 4 Buffer Memory Areas