Setting procedure
■Sampling processing
Set "Average processing setting" to "Sampling processing".
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Module Parameter]  [Basic
setting]  [Conversion system]
■Average processing
1.
Set "Average processing setting" to "Time average", "Count average", or "Moving average".
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Module Parameter]  [Basic
setting]  [Conversion system]
2.
Set a value for "Time average/Count average/Moving average setting".
Item
*1
Time average
Count average
Moving average
*1 Set a value greater than the value calculated by the following formula as the time average.
Conversion speed  Number of conversion enabled channels  Minimum processing times (4 times)
3 FX5-8AD
344
3.4 Functions
Setting range
When the input type is current, and voltage: 4 to 10000 (ms)
When the input type is resistance temperature detector, and thermocouple: 160 to 10000 (ms)
4 to 10000 (times)
2 to 1000 (times)