CH1 Logging cycle unit setting
Set a cycle unit for storing the logging data.
For details on the logging function, refer to the following.
Page 59 Logging function
Setting value
0
1
2
• Setting a value out of the above range causes a logging cycle setting value range error (error code: 1D1H). Logging
cannot be performed.
• If the set logging cycle is below the update cycle of data to be logged, a logging cycle setting disable error (error code:
1D2H) occurs. Logging cannot be performed.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Logging cycle unit setting
CH Logging cycle unit setting (In FX3
allocation mode function)
■Enabling the setting
Turn offonoff 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■Default value
The default is ms (1) for all channels.
CH1 Logging points after trigger
Set a number of data points collected for the time period from the occurrence of a hold trigger to the logging stop.
For details on the logging function, refer to the following.
Page 59 Logging function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Post-trigger logging points
CH Post-trigger logging points (In FX3
allocation mode function)
■Setting range
The possible setting range is from 1 to 10000.
Setting a value out of the range causes a post-trigger logging points setting range error (error code: 1D4H). Logging cannot
be performed.
When 'CH1 Logging enable/disable setting' (Un\G535) is set to Disable (1), the setting for 'CH1 Post-trigger logging points'
(Un\G539) is ignored.
■Enabling the setting
Turn offonoff 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■Default value
The default value is 5000 for all channels.
Setting content
s
ms
s
CH1
CH2
538
738
9191
9192
CH1
CH2
539
739
9201
9202
CH3
CH4
938
1138
9193
9194
CH3
CH4
939
1139
9203
9204
Appendix 4 Buffer Memory Areas