CH1 Alarm output lower limit value
Set the range of a digital value used for alarm output.
For the alarm output function, refer to the following.
Page 193 Alert output function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Alarm output lower limit value
CH Alarm output lower limit value (in FX3
allocation mode function)
■Setting range
The possible setting range is from -32768 to +32767. A channel for which any value not meeting the condition of "alarm output
upper limit value > alarm output lower limit value" causes an alarm output upper/lower limit value reverse error (error code:
1B1H).
If 'CH1 alarm output setting' (Un\G508) is set to Disable (1), the setting for 'CH1 alarm output lower limit value' (Un\G512) will
be ignored.
■Enabling the setting
Turn on and off 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■Default value
The default value is 0 for all channels.
■Precautions
When the shift function is used, always set a value in consideration of 'CH1 Input value shift amount' (Un\G480).
CH1 Increase digital limit value
Set the increment value per conversion cycle (80 s) when using the rate control function.
For the rate control function, refer to the following.
Page 195 Rate control function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Increase digital limit value
CH Increase digital limit value (in FX3
allocation mode function)
■Setting range
The setting range is from 0 to 64000 (FA00H). If a value out of the setting range is set for a channel where the conversion and
rate control are enabled, a digital limit value range error (error code: 1B9H) occurs.
When the scaling setting is enabled, the increase digital limit value of the input digital value converted within the scaling range
is applied.
■Enabling the setting
Turn on and off 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■Default value
The default value is 64000 for all channels.
■Precautions
When a value exceeding 32767 is set in 'CH1 Increase digital limit value' (Un\G514) with the program, the value must be input
in hexadecimal.
CH1
CH2
512
712
41
42
CH1
CH2
514
714
3340
3342
CH3
CH4
912
1112
43
44
CH3
CH4
914
1114
3344
3346
Appendix 8 Buffer Memory Areas
A
APPX
317