Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 213

Analog control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

• For Enable (output limited)
If Output setting during wave output stop is Output value during wave output stop (2), this function outputs the value that was
set with the Output value during wave output stop while the wave output is at a stop.
By starting the wave output, warning output is performed, and the value set by the warning output upper and limit values is
output.
CH1 Output enable/disable flag
(Un\G70, b1)
CH1 Wave output start/stop
request (Un\G462)
CH1 Wave output status monitor
(Un\G401)
'Warning output signal'
(Un\G69, b14)
Wave data
Digital value
Warning output
Upper limit value
Warning output
Lower limit value
Output value selected with CH1
Output setting during wave output stop (Un\G524)
Since the wave output is at a stop, the alarm turns off. (The warning doesn't turn on.)
When the output is in the range equal to or larger than "Warning output lower limit value" or equal to or smaller than "Warning output upper limit
value", the alarm can be turned off using 'Warning output clear request' (Un\G70, b14).
Since the wave output is at a stop, the alarm can be turned off using 'Warning output clear request' (Un\G70, b14).
OFF
Wave output stop request (0)
Wave output stopped (0)
ON
OFF
Analog output
CH1 Alert output
upper limit value
(Un\G510)
CH1 Alert output
lower limit value
(Un\G512)
Offset value
ON
Wave output start request (1)
Wave output in progress (1)
2.4 Functions
2
Wave output stopped (0)
2 FX5-4DA
211