Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 485

Analog control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

CH1 Input type/range setting [FX2N allocation mode]
When the FX2N allocation mode function is used, this area is for setting an input type and range setting.
b15
CH1 to 4 input type/range setting
(Un\G0)
b15
CH5 to 8 input type/range setting
(Un\G1)
Setting value (Hexadecimal)
0FH
00H
01H
02H
03H
04H
05H
06H
07H
08H
09H
0AH
0BH
0CH
0DH
0EH
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Input type/range setting (In FX2N allocation mode
function)
■Enabling the setting
Turn offonoff 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■Default value
The default value is conversion disabled (0FH).
to
b12 b11
to
b8 b7
CH4
CH3
to
b12 b11
to
b8 b7
CH8
CH7
Input type
Conversion disable
Voltage
Current
Thermocouple
CH1
CH2
0
to
b4
b3
to
b0
CH2
CH1
to
b4
b3
to
b0
CH6
CH5
Input range
-10 to +10 V
4 to 20 mA
-20 to +20 mA
Thermocouple K
Thermocouple J
Thermocouple T
Thermocouple K
Thermocouple J
Thermocouple T
CH3
CH4
CH5
1
Appendix 12 Buffer Memory Areas
CH6
CH7
CH8
APPX
483
A

Advertisement

Table of Contents
loading

Table of Contents