Setting example
Ex.
An example of the following settings is shown below.
Item
Range setting
Scaling enable/disable setting
Scaling upper limit value
Scaling lower limit value
Digital value
32000
Scaling upper limit value 20000
Scaling lower limit value 4000
Input voltage (V)
0
1
2
3
4
5
Ex.
An example of the following settings is shown below.
Item
Range setting
Scaling enable/disable setting
Scaling upper limit value
Scaling lower limit value
Input voltage and scaling value become as follows.
Digital value
+32000
Scaling upper limit value 20000
Scaling lower limit value 4000
-32000
Analog input voltage (V)
-10
-5
0
+5
+10
Setting
Voltage (0 to 5 V)
Enable
20000
4000
(1)
(2)
0
Analog input voltage (V)
0
5
(1) Digital output value
0
6400
12800
19200
25600
32000
Setting
Voltage (-10 to +10 V)
Enable
20000
4000
(1)
(2)
0
Analog input voltage (V)
-10
0
+10
(1) Digital output value
-32000
-16000
0
+16000
+32000
(2) Digital operation value (scaling value)
4000
7200
10400
13600
16800
20000
(2) Digital operation value (scaling value)
4000
8000
12000
16000
20000