Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 483

Analog control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

CH1 Gain setting value
As Channel change request (Un\G70, b11) is turned offonoff in offset/gain setting mode, the measured temperature value
is corrected by a value written in this area.
Specify the value of a 16-bit signed binary number.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Gain setting value
CH Gain setting value (In FX2N allocation mode function)
■Setting range
Input type
Resistance temperature detector
*1
Thermocouple
*1 In the case of FX2N allocation mode, only thermocouple K, J and T are setting enabled.
Setting a value out of the range causes an offset/gain temperature setting value range error (error code: 1ECH).
'CH1 Offset setting value' (Un\G562) and 'CH1 Gain setting value' (Un\G564) must be set to be within the following
temperature input range:
• Offset setting value < Gain setting value
A channel where the set value is out of the above range causes an offset/gain temperature setting value setting error (error
code: 1E9H).
■Default value
The default value is set to 0.
• An effective way to achieve high accuracy is to set up error correction in 'CH1 Offset setting value'
(Un\G562) and 'CH1 Gain setting value' (Un\G564) assuming the minimum and maximum temperatures of
the used range.
• Configure 'CH1 Offset setting value' (Un\G562) and 'CH1 Gain setting value' (Un\G564) while reading out
digital output values.
CH1
564
1301
Input range
Pt100
Ni100
Thermocouple K
Thermocouple J
Thermocouple T
Thermocouple B
Thermocouple R
Thermocouple S
CH2
CH3
CH4
CH5
764
964
1164
1364
1302
1303
1304
1305
Celsius/Fahrenheit display
setting
Celsius
Fahrenheit
Celsius
Fahrenheit
Celsius
Fahrenheit
Celsius
Fahrenheit
Celsius
Fahrenheit
Celsius
Fahrenheit
Celsius
Fahrenheit
Celsius
Fahrenheit
Appendix 12 Buffer Memory Areas
CH6
CH7
CH8
1564
1764
1964
1306
1307
1308
Setting range
-2000 to +8500
-3280 to +15620
-600 to +2500
-760 to +4820
-2700 to +13700
-4540 to +24980
-2100 to +11300
-3460 to +20660
-2700 to +4000
-4540 to +7520
0 to 17100
320 to 31100
-500 to +17100
-580 to +31100
-500 to +17100
-580 to +31100