CH1 Input signal error detection upper limit setting value
Set a value to detect an error for the input analog value.
For details on the input signal error detection function, refer to the following.
Page 53 Input signal error detection function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Input signal error detection upper limit
setting value
CH Input signal error detection upper limit
setting value (In FX3 allocation mode function)
■Setting range
The possible setting range is from 0 to 250 (0 to 25.0%). Set it in a unit of 1 (0.1%).
In the channel where a value out of the above setting range is set, an input signal error detection setting value range error
(error code: 1C1H) occurs.
The input signal error detection upper limit value is calculated by using the input signal error detection upper limit set value as
the reference as follows. The input signal error detection upper limit value to be calculated varies depending on the input
range used.
• Input signal error detection upper limit value = Gain value of each range + (Gain value of each range - Offset value of each
range)  (Input signal error detection upper limit setting value/1000)
Detection conditions vary depending on 'CH1 Input signal error detection setting' (Un\G528) as follows:
• When Input signal error detection setting is set to Upper and lower limit detection (1), the detection is performed with both
the input signal error detection upper limit value and input signal error detection lower limit value.
• When 'Input signal error detection setting' is set to Lower limit detection (2), the value set in this area is ignored.
• When Input signal error detection setting is set to Upper limit detection (3), the detection is performed only with the input
signal error detection upper limit value.
• When Input signal error detection setting is set to Simple disconnection detection (4), the value set in this area is ignored.
■Enabling the setting
Turn offonoff 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■Default value
The default value is 50 for all channels. When the FX3 allocation mode function is used, 20 is set for all channels.
CH1 Logging enable/disable setting
Set whether to enable or disable the logging function.
For details on the logging function, refer to the following.
Page 59 Logging function
Setting value
0
1
Setting a value other than the above causes a logging enable/disable setting range error (error code: 1D0H).
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Logging enable/disable setting
CH Logging enable/disable setting (In FX3
allocation mode function)
■Enabling the setting
Turn offonoff 'Operating condition setting request' (Un\G70, b9) to enable the setting.
CH1
CH2
530
730
1171
1172
Setting content
Enable
Disable
CH1
CH2
535
735
9161
9162
CH3
CH4
930
1130
1173
1174
CH3
CH4
935
1135
9163
9164
Appendix 4 Buffer Memory Areas
A
APPX
163