Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 44

Analog control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

■Operations when an input signal error occurs
When an input signal error occurs, even if 'CH1 Difference conversion trigger' (Un\G470) changes from No request (0) to
Trigger request (1), the difference conversion does not start. After the input signal error returns to the normal value, change
'CH1 Difference conversion trigger' (Un\G470) from No request (0) to Trigger request (1) again. If an input signal error occurs
in the status of Trigger request (1), the difference conversion starts at the timing when the input signal error returns to the
normal value, treating the digital operation value as the difference conversion reference value.
Analog input value (mA)
2.2
'Input signal error detection
flag' (Un\G40)
'Input signal error detection
signal' (Un\G69, b12)
'CH1 Difference conversion
trigger' (Un\G470)
'CH1 Difference conversion
standard value' (Un\G432)
'CH1 Difference conversion
status flag' (Un\G408)
1 FX5-4AD
42
1.4 Functions
4
CH1 Analog input value
2
Input signal error is occurring.
0
ON
OFF
OFF
No request (0)
0
Not converted (0)
ON
Trigger request (1)
Digital value corresponding to 2.2 mA
Converting difference (1)
Detection range
Outside detection range
Included
Time
Timing when input signal returns to
the normal value

Advertisement