Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 219

Analog control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

• For CLEAR
While the wave output is at a stop, the offset value is output.
CPU module status
CH1 D/A conversion
enable/disable setting (Un\G500)
CH1 Output enable/disable flag
(Un\G70, b1)
CH1 Wave output start/stop
request (Un\G462)
CH1 Wave output status monitor
(Un\G401)
Wave data
Output value as per the setting of CH1
Output setting during wave output stop (Un\G524)
• Wave output start request is accepted only when the CPU module status is RUN. If 'CH1 Wave output start/
stop request' (Un\G462) is changed to Wave output start request (1) in CPU module status other than RUN,
the wave output will not start.
• Wave output pause request is accepted only when the CPU module status is RUN or STOP.
• Wave output pause request is accepted only when the CPU module status is RUN.
• If 'CH1 Wave output start/stop request' (Un\G462) is set to a value other than 0 to 2, an error will occur. A
logging cycle setting disable error (error code: 1D0H) is stored in 'Latest error code' (Un\G0), 'Error flag'
(Un\G69, b15) and the ERROR LED turn on. In this case, the wave output will continue.
• An attempt to output a value out of the digital value range set with the output range causes an error,
resulting in occurrence of a digital value setting range error (error code: 191H).
■Checking the wave output function status
The wave output function status can be checked with the following buffer memory addresses.
Item
Wave output status monitor
Wave output conversion cycle
monitor
Wave output count monitor
Wave output current address
monitor
Wave output current digital value
monitor
Wave output digital value out-of-
range address monitor
Wave output alarm occurrence
address monitor
For details on the buffer memory areas, refer to the following.
Page 292 Details of buffer memory addresses
OFF
Wave output
Wave output stop request (0)
start request (1)
Wave output
Wave output stopped (0)
in progress (1)
Analog output
Offset value
Description
An area to store the wave output status.
Area in which the conversion cycle of wave output is stored. The unit of the stored value is s.
An area to store the number of times the wave pattern was output.
An area to store the buffer memory address of the currently output wave data.
An area to store the currently output digital input value.
When wave data that contains a registered digital input value out of the setting range is output, this area is used to store
the registration destination buffer memory address of that wave data. When a digital value outside the setting range is
detected with multiple pieces of wave data, this area stores the buffer memory address of only the first detected piece of
data.
An area to store the buffer memory address of the wave data when an alarm occurred. When an alarm occurs due to
multiple pieces of wave data, only the buffer memory address of the wave data causing the first alarm is stored.
RUN
D/A conversion enable (0)
ON
Wave output
pause request (2)
Wave output paused (2)
In the case of CLEAR,
the offset value is output.
Wave output start request (1)
Wave output stopped (0)
Wave output
in progress
(1)
2 FX5-4DA
2.4 Functions
2
217

Advertisement

Table of Contents
loading

Table of Contents