Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 34

Analog control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

Setting procedure
■Sampling processing
Set "Average processing setting" to "Sampling processing".
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Module Parameter]  [Basic
setting]  [A/D conversion method]
■Averaging processing and Primary delay filter
1.
Set "Average processing setting" to "Time average", "Count average", "Moving average", or "Primary delay filter".
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Module Parameter]  [Basic
setting]  [A/D conversion method]
2.
Set a value for "Time average/Count average/Moving average/Primary delay filter constant setting".
Item
Time average
Count average
Moving average
Primary delay filter
■Digital filter
1.
Set "Average process specification" to "Digital filter".
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Module Parameter]  [Basic
setting]  [A/D conversion method]
2.
Set a value for "Digital filter setting".
Item
Digital filter setting
3.
Set "Digital filter fluctuation range setting".
Item
Digital filter fluctuation range setting
*1 For the digital filter fluctuation range setting, set a value equal to or larger than [Number of A/D conversion enabled channels 
Conversion speed].
If a value less than [Number of A/D conversion enabled channels  Conversion speed] is set when the digital filter fluctuation range
setting is within the setting range, it will operate with sampling processing without performing digital filtering.
1 FX5-4AD
32
1.4 Functions
Setting range
2 to 5000 (ms)
4 to 62500 (counts)
2 to 1000 (counts)
1 to 500 (times)
Setting range
1 to 1600 (digits)
Setting range
*1
80 to 200000 (s)

Advertisement

Table of Contents
loading

Table of Contents