Input signals
A state of an analog input module can be checked in the buffer memory area.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
Input signals
Input signal (In FX3 allocation mode function)
■List of input signals
Buffer Memory Areas
b0
b1 to 4
b5
b6
b7
b8
b9
b10
b11
b12
b13
b14
b15
■Module READY (b0)
Module READY (X0) turns on to indicate the preparation for the A/D conversion is completed after the power-on or reset of the
CPU module, and the A/D conversion is performed.
In the following cases, 'Module READY' turns off.
• In the offset/gain setting mode (In this case, the A/D conversion is performed.)
• When a watchdog timer error has occurred in the analog input module (In this case, the A/D conversion is not performed.)
■Offset/gain initialization completed flag (b5)
• Use as an interlock condition to turn offonoff 'Offset/gain initialization request' (Un\G70, b5).
• Offset/gain initialization is not be performed unless 'Offset/gain initialization enabled code '(Un\G305) is set to E20FH.
• It is possible to perform offset/gain initialization in offset/gain setting mode only.
• When 'Offset/gain initialization request' (Un\G70, b5) is off, 'Offset/gain initialization complete flag' (Un\G69, b5) turns off.
Offset/Gain setting offset value
Offset/Gain setting gain value
'Offset/gain initialization completed flag'
(Un\G69, b5)
'Offset/gain initialization request'
(Un\G70, b5)
APPX
130
Appendix 4 Buffer Memory Areas
CH1
69
69
Description
Module READY
Use not allowed
Offset/gain initialization completed flag
Use not allowed
Use not allowed
Warning output signal
Operating condition setting completed flag
Offset/gain setting mode status flag
Channel change completed flag
Input signal error detection signal
Range switching complete flag
A/D conversion completed flag
Error flag
Controlled by the analog input module
Controlled by the program
Value other than initial value
Value other than initial value
OFF