Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 221

Analog control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

■If the CPU module status was changed during output
When the CPU module status was changed during wave output, after terminating the wave output, it operates as follows
depending on the analog output HOLD/CLEAR function setting.
• For the previous value
If the CPU changes from RUN to STOP, the wave output terminates and the value immediately before STOP is held. When
'CH1 Output enable/disable flag' (Un\G70, b1) is turned on with the CPU module changed from STOP to RUN, the output
changes as per the setting of 'CH1 Output setting during wave output stop' (Un\G524). Wave output does not restart.
To restart the wave output, change 'CH1 Wave output start/stop request' (Un\G462) from Wave output stop request (0) to
Wave output start request (1) again.
CPU module status
CH1 D/A conversion
enable/disable setting (Un\G500)
CH1 Output enable/disable flag
(Un\G70, b1)
CH1 Wave output start/stop
request (Un\G462)
CH1 Wave output status monitor
(Un\G401)
Wave data
Output value as per the setting of CH1 Output
setting during wave output stop (Un\G524)
The output is disabled because the CPU module changes from RUN to STOP.
Once the HOLD/CLEAR operates, the wave output stops.
Wave output does not restart.
To restart the wave output, change the setting to Wave output start request (1).
RUN
OFF
ON
Wave output stop request (0)
Wave output stopped (0)
Analog output
Offset value
0 V/0 mA
STOP
D/A conversion enable (0)
OFF
Wave output start request (1)
Wave output stop request (0)
Wave output
Wave output stopped (0)
in progress (1)
Previous value
RUN
ON
Wave output start request (1)
Wave output in progress (1)
2 FX5-4DA
2.4 Functions
2
219