Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 45

Analog control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

■Operation performed when the operation condition setting request (Un\G70, b9) is turned
offonoff
• During the difference conversion, even when 'Operating condition setting request' (Un\G70, b9) is turned offonoff, the
difference conversion continues without updating the difference conversion reference value. To update the difference
conversion reference value, restart the difference conversion by changing CH1 Difference conversion trigger (Un\G470)
from Trigger request (1) to No request (0), and Trigger request (1) again.
• CH1 Difference conversion trigger (Un\G470) does not become valid even when the trigger changes from No request (0) to
Trigger request (1) when 'Operating condition setting request' (Un\G70, b9) is turned offon. After turning offonoff
Operating condition setting request (Un\G70, b9), change CH1 Difference conversion trigger (Un\G470) from No request
(0) to Trigger request (1) again.
'Operating condition setting request'
(Un\G70, b9)
'Operating condition setting completed
flag' (Un\G69, b9)
'CH1 Difference conversion trigger'
(Un\G470)
CH1 Digital operation value before
difference conversion
'CH1 Difference conversion standard
value' (Un\G432)
'CH1 Digital operation value'
(Un\G402)
'CH1 Difference conversion status flag'
(Un\G408)
ON
OFF
ON
OFF
Trigger request (1)
9950
10001 10100 10010 10510 12000 12100 13250
10000
10000 10000 10000 10000 10000 10000 10000
Not updated
-50
1
100
10
510
Converting difference (1)
No request (0)
Trigger request (1)
13000
13310
Updated
13000
13000
2000 12100 13250
0
310
Not converted (0)
Converting difference (1)
1
1 FX5-4AD
43
1.4 Functions

Advertisement

Table of Contents
loading