Troubleshooting; Troubleshooting With The Leds - Mitsubishi Electric MELSEC iQ-F FX5 User Manual

Analog control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

2.10

Troubleshooting

This section describes errors that may occur during use of an analog output module and troubleshooting for these.

Troubleshooting with the LEDs

Check the state of the LEDs to narrow down the possible causes of the trouble. This step is the first diagnostics before using
GX Works3.
The analog output module state can be checked with the POWER, RUN, ERROR, and ALM LEDs. The following table shows
the correspondence between the LEDs and the analog output module state.
Name
Description
POWER LED
Indicates the power supply status.
ON: Power ON
OFF: Power off or module failure
RUN LED
Indicates the operating status.
Light on: Normal operation
Flashing: Offset/gain setting mode
Light off: Error occurring
ERROR LED
Indicates the error status.
ON: Minor error
Flashing: Moderate error or major error
OFF: Normal operation
ALM LED
Indicates the alarm status.
ON: Alarm occurred
OFF: Normal operation
*1 For details, refer to the following.
Page 273 List of error codes
*2 For details, refer to the following.
Page 276 List of alarm codes
*1
*2
2 FX5-4DA
269
2.10 Troubleshooting
2

Advertisement

Table of Contents
loading

Table of Contents