Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 166

Analog control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

■Default value
The default value is Disable (1) for all the channels.
CH1 Logging data setting
Determine the target to be collected: digital output value or digital operation value.
For details on the logging function, refer to the following.
Page 59 Logging function
Setting value
0
1
Setting a value other than the above causes a logging data setting range error (error code: 1D3H).
When 'CH1 Logging enable/disable setting' (Un\G535) is set to Disable (1), the setting for 'CH1 Logging data setting'
(Un\G536) is ignored.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Logging data setting
CH Logging data setting (in FX3 allocation
mode function)
■Enabling the setting
Turn offonoff 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■Default value
The default value is Digital operation value (1) for all channels.
CH1 Logging cycle setting value
Set a cycle for storing the logging data.
For details on the logging function, refer to the following.
Page 59 Logging function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Logging cycle setting value
CH Logging cycle setting value (In FX3
allocation mode function)
■Setting range
The setting range varies depending on the setting in 'CH1 Logging cycle unit setting' (Un\G538).
CH1 Logging cycle unit setting (Un\G538)
s (0)
ms (1)
s (2)
• Setting a value out of the above range causes a logging cycle setting value range error (error code: 1D1H). Logging
cannot be performed.
• If the set logging cycle is below the update cycle of data to be logged, a logging cycle setting disable error (error code:
1D2H) occurs. Logging cannot be performed.
■Enabling the setting
Turn offonoff 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■Default value
The default value is 4 for all channels.
APPX
164
Appendix 4 Buffer Memory Areas
Setting content
Digital output value
Digital operation value
CH1
CH2
536
736
9171
9172
CH1
CH2
537
737
9181
9182
Setting range
80 to 32767
1 to 32767
1 to 3600
CH3
CH4
936
1136
9173
9174
CH3
CH4
937
1137
9183
9184