Warning output flag (Process alarm upper limit/lower limit) [FX3 allocation mode]
When the FX3 allocation mode function is used, the upper/lower limit alarm of the process alarm can be checked.
b15 b14 b13 b12 b11 b10 b9
0
0
0
0
0
(2)
(1) 0: Normal, 1: Alarm ON
(2) The values of b8 to b15 are fixed to 0.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
Warning output flag (Process alarm) (in FX3
allocation mode function)
■Alert output flag status
• When the value is equal to or exceeds the limit specified by the process alarm upper upper limit value or is equal to or falls
below the process alarm lower lower limit value, Alarm ON (1) is stored in Warning output flag (Process alarm)
corresponding to each channel.
• If an alert is detected even in one channel, of the channels where conversion is enabled and the alert output setting
(Process alarm) is enabled, 'Alert output signal' (Un\G69, b8) also turns on.
■Clearing Alert output flag
• When the digital operation value returns within the setting range, the flag is automatically cleared.
• Turning offonoff 'Operating condition setting request' (Un\G70, b9) allows the flag to be cleared.
Warning output flag (Rate alarm upper limit)
The upper limit alarm of the rate alarm can be checked for each channel.
b15 b14 b13 b12 b11 b10 b9
0
0
0
0
0
(1) 0: Normal, 1: Alarm ON
(2) The values of b4 to b15 are fixed to 0.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
Warning output flag (Rate alarm upper limit)
■Alert output flag status
• If the limit specified in the rate alarm upper limit value is equal to or exceeded, Alarm ON (1) is stored in 'Alert output flag
(Rate alarm upper limit)' (Un\G38) of the corresponding channel.
• If an alert is detected even in one channel, of the channels where conversion is enabled and the alert output setting (Rate
alarm) is enabled, 'Alert output signal' (Un\G69, b8) also turns on.
■Clearing Alert output flag
• When the change rate of the digital output value returns within the setting range, the flag is automatically cleared.
• Turning offonoff 'Operating condition setting request' (Un\G70, b9) allows the flag to be cleared.
APPX
126
Appendix 4 Buffer Memory Areas
b8
b7
b6
b5
b4
CH4 CH4
CH3
CH3
Upper
Lower
Upper
Lower
0
0
0
limit
limit
limit
limit
value
value
value
value
CH1
26
b8
b7
b6
b5
b4
0
0
0
0
0
0
0
(2)
CH1
38
b3
b2
b1
b0
CH2
CH2 CH1
CH1
Upper
Lower
Upper
Lower
limit
limit
limit
limit
value
value
value
value
(1)
CH2
b3
b2
b1
b0
CH4
CH3
CH2
CH1
(1)
CH2
CH3
CH4
CH3
CH4

Advertisement

Table of Contents
loading

Table of Contents