CH1 Process alarm upper upper limit value
Set an upper upper limit value of the alert output function (Process alarm).
For details on the alert output function, refer to the following.
Page 354 Alert output function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Process alarm upper upper limit value
CH Process alarm upper upper limit value (in FX2N
allocation mode function)
■Setting range
The possible setting range is from -32768 to +32767.
■Enabling the setting
Turn offonoff 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■Default value
The default value is set to 0.
CH1 Process alarm upper lower limit value
Set an upper lower limit value of the alert output function (Process alarm).
For details on the alert output function, refer to the following.
Page 354 Alert output function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Process alarm upper lower limit value
CH Process alarm upper lower limit value (in FX2N
allocation mode function)
■Setting range
The possible setting range is from -32768 to +32767.
■Enabling the setting
Turn offonoff 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■Default value
The default value is set to 0.
APPX
468
Appendix 12 Buffer Memory Areas
CH1
CH2
CH3
514
714
914
81
82
83
CH1
CH2
CH3
516
716
916
1191
1192
1193
CH4
CH5
CH6
1114
1314
1514
84
85
86
CH4
CH5
CH6
1116
1316
1516
1194
1195
1196
CH7
CH8
1714
1914
87
88
CH7
CH8
1716
1916
1197
1198

Advertisement