■Offset/gain initialization completed flag (b5)
• Use as an interlock condition to turn offonoff 'Offset/gain initialization request' (Un\G70, b5).
• Offset/gain initialization is not be performed unless 'Offset/gain initialization enabled code '(Un\G305) is set to E20FH.
• It is possible to perform offset/gain initialization in normal mode only.
• When 'Offset/gain initialization request' (Un\G70, b5) is off, 'Offset/gain initialization complete flag' (Un\G69, b5) turns off.
Offset value in offset/gain setting
Gain value in offset/gain setting
'Offset/gain initialization completed flag'
(Un\G69, b5)
'Offset/gain initialization request'
(Un\G70, b5)
■Disconnection detection signal (b6)
Turns on when disconnection is detected for the channel where Enable (0) is set in 'CH1 Disconnection detection enable/
disable setting' (Un\G531) and the conversion is enabled.
When 'Disconnection detection signal' (Un\G69, b6) turns on, the following operations are performed.
• A value corresponding to 'CH1 Conversion setting at disconnection detection' (Un\G534) is stored in the temperature
measurement value of the relevant channel.
• The ALM LED flashes.
Turning off 'Disconnection detection signal' (Un\G69, b6) differs depending on Input signal error/disconnection detection auto-
clear enable/disable setting.
Input signal error/
Disconnection
detection automatic
clear enable/disable
setting
Enable (0)
Disable (1)
Averaging processing starts over after the conversion resumes.
APPX
444
Appendix 12 Buffer Memory Areas
Implement by multiple input module
Implement by program
Value other than initial value
Value other than initial value
OFF
OFF
Operations related to the turning off of Disconnection detection signal (Un\G69, b6)
When the temperature input value is within the setting range and the disconnection is restored, the 'Disconnection detection
signal' (Un\G69, b6) automatically turns off, and ALM LED turns off.
Eliminate the disconnection cause, and turn 'Error clear request' (Un\G70, b15) offonoff. 'Disconnection detection signal'
(Un\G69, b6) turns off, ALM LED turns off, and the latest alarm code is cleared.
Disconnection
0
detection flag
'Disconnection
detection signal'
OFF
(Un\G69, b6)
'Error clear request'
OFF
(Un\G70, b15)
Initial value
Initial value
Implement by multiple input module
Implement by program
Disconnection detection
ON
ON
0
OFF
OFF