MX960 3D Universal Edge Router Hardware Guide
198
Table 96: Mounting Hardware Hole Locations for Front-Mounting in an
Open-Frame Rack
Hole
Distance Above U Division
30
17.26 in. (43.8 cm)
27
15.51 in. (39.4 cm)
24
13.76 in. (34.9 cm)
21
12.01 in. (30.5 cm)
18
10.26 in. (26.0 cm)
15
8.51 in. (21.6 cm)
12
6.76 in. (17.1 cm)
9
5.01 in. (12.7 cm)
6
3.26 in. (8.3 cm)
3
1.51 in. (3.8 cm)
2
0.88 in. (2.2 cm)
1
0.25 in. (0.6 cm)
To install the large mounting shelf (see
On the rear of each rack rail, install cage nuts, if needed, in the holes specified in
1.
Table 96 on page 198
for the large shelf.
Partially insert a mounting screw into the highest hole specified in
2.
Hange the shelf over the mounting screws using the keyhole slots located near the
3.
top of the large shelf flanges.
Partially insert screws into the open holes in the flanges of the large shelf.
4.
Tighten all the screws completely.
5.
Large Shelf
9.86 U
X
8.86 U
X
7.86 U
X
6.86 U
X
5.86 U
X
4.86 U
X
3.86 U
X
2.86 U
X
1.86 U
X
0.86 U
X
0.50 U
X
0.14 U
Figure 53 on page
Copyright © 2017, Juniper Networks, Inc.
199):
Table 96 on page
198.