Copyright © 2017, Juniper Networks, Inc.
Tighten the cable restraint captive screw to hold the power cables in place.
13.
WARNING:
Once the DC power supply is connected, the cable will be
blocking the PEM slot label. Make sure and note or mark the PEM slot once
the power supply is connected.
Replace the clear plastic cover over the terminal studs on the faceplate.
14.
Verify that the power cabling is correct, that the cables are not touching, and that they
15.
do not block access to router components or drape where people could trip on them.
Switch on the dedicated customer site circuit breaker.
16.
Verify that the
INPUT OK
17.
On each of the DC power supplies, switch the DC circuit breaker to the center position
18.
before moving it to the on (
NOTE:
The circuit breaker may bounce back to the off (
move the breaker too quickly.
Verify that the
BREAKER ON
19.
Verify that the
PWR OK
20.
LED on the power supply is lit steadily.
) position.
|
LED is lit steadily.
LED is lit steadily.
Chapter 21: Installing Components
) position if you
O
295