Table 64: Router Environmental Specifications

Description
Altitude
Relative humidity
Temperature
Seismic
Maximum thermal output
NOTE:
Install the router only in restricted areas, such as dedicated equipment
rooms and equipment closets, in accordance with Articles 110-16, 110-17, and
110-18 of the National Electrical Code, ANSI/NFPA 70.
Tools and Parts Required to Maintain the MX960 Router on page 445
Definition of Safety Warning Levels
The checklist in
Table 65 on page 124
preparing a site for router installation.
For More Information
"MX960 Router Environmental
Specifications" on page 124
Value
No performance degradation to 10,000 ft (4038 m)
Normal operation ensured in relative humidity range of 5% to 90%,
noncondensing
Normal operation ensured in temperature range of 32°F (0°C) to
104°F (40°C)
Nonoperating storage temperature in shipping container:
–40°F (–40°C) to 158°F (70°C)
Designed to meet Telcordia Technologies Zone 4 earthquake
requirements
AC power: 27,007 BTU/hour (7920 W)
DC power: 18,987 BTU/hour (5568 W)