11. OPTIONS AND PERIPHERAL EQUIPMENT
(d) Noise reduction techniques for the network cable
When using it in an environment with excessive noise, directly connect the shield of the network
cable to the ground plate with cable clamp fittings at a place 200 mm to 300 mm or less from the
servo amplifier.
When connecting the network cable from outside the cabinet, connect it to the ground plate at a
place 5 mm to 10 mm away from the cabinet entrance.
To reinforce measures against noise, it is recommended to install a data line filter (TDK ZCAT1730-
0730) to the network cable. Install the data line filter to a place 80 mm or less from the servo
amplifier.
1) For inside the cabinet
a) When using cable clamp fittings
b) When using a data line filter
2) For outside the cabinet
a) When using cable clamp fittings
b) When using a data line filter
POINT
Take measures against noise for both ends of the network cable.
Servo amplifier
Servo amplifier
Servo amplifier
Servo amplifier
200 mm to 300 mm or less
Data line filter
80 mm or less
Inside the
cabinet
Cable clamp fitting
Locate 5 mm to 10 mm away
from the cabinet entrance.
Inside the
cabinet
Data line filter
80 mm or less
11 - 80
Cable clamp fitting
Outside the
cabinet
Outside the
cabinet