Group 3: Software Zones
Type ID
FZON
RZON
• A Forward-Activating Zone is a software zone in control panel memory which once activated by an
addressable input device or other forward zone may in turn activate other zones and/or addressable
output devices directly. Zones and output devices activated by a forward zone are contained in the CBE
List of that forward zone, or the zone may be listed in the CBE of the addressable output device.
• A Reverse-Activating Zone is a software zone in control panel memory which if not activated directly
by an addressable input device or forward zone may be activated through an associated CBE equation.
A Reverse
Group 4: Alarm Initiation Modules
Type ID
MON
MPUL
NCMN
NOA
NONA
PULL
SCON
WAT
3-54
www.PDF-Zoo.com
Display Label
FORWARD ZONE
A software-defined zone that is forward-activating .
REVERSE ZONE
A software-defined zone that is reverse-activating.
Zone may be listed in other CBE Equations.
Display Label
MONITOR
MMX Monitor Module, an XPM-8 circuit, or an XP5-M circuit used to
monitor normally-open contact, shorting-type devices other than 4-wire
smoke detectors (i.e. conventional heat detectors, pull stations, etc.).
MON PULL STA
BGX-101L Addressable Manual Pull Station.
MON NORM CLD
MMX Monitor Module, an XPM-8 circuit, or an XP5-M circuit used to
monitor normally-closed contact, opening-type devices.
NON ALARM
MMX Monitor Module, an XPM-8 circuit, or an XP5-M circuit that
functions identically to Software Type ID NONA with one exception -
subsequent alarms from this Type ID will not reactivate silenced output
devices - once silenced, outputs will remain silenced until reactivated by
another Software Type ID (or cleared by System Reset and reactivated).
NON ALM MON
MMX Monitor Module, an XPM-8 circuit, or an XP5-M circuit used to
monitor normally-open contact, shorting-type non-alarm devices. Activa-
tion of a module with Software Type ID NONA will not initiate a fire alarm
condition:
PULL STATION
BGX-10 Addressable Manual Pull Station.
SMOKE (CONV)
MMX Monitor Module or an XP5-M circuit used to monitor conventional
4-wire smoke detectors. This module has a longer reset period than
modules programmed as MON.
WATER FLOW
MMX Monitor Module, an XPM-8 circuit, or an XP5-M circuit dedicated
to a Water Flow Alarm device.
Type of Device
Type of Device
• System Alarm LED will not illuminate.
• Does not activate alarm status line count on a CRT.
• No affect on modules programmed as APND (alarm pending)
or GPND (general event pending).
• Alarm, clear alarm, or acknowledgments are not reported for
this type.