Notifier AM2020 User Manual page 123

Fire alarm control panel
Hide thumbs Also See for AM2020:
Table of Contents

Advertisement

Menu Choice 8:
Enter Option Choice:
Operating 15088:J 10/22/99
www.PDF-Zoo.com
ISIB=Y
1
THESE ANNUNCIATORS ARE INSTALLED:
2
(PRESS ENTER TO CONTINUE UNTIL DONE)
1=Y, 2=N, 3=N, 4=N, 5=Y, 6=Y, 7=N, 8=N,
9=Y,10=N,11=N,12=Y,13=Y,14=Y,15=N,16=N,
17=Y,18=Y,19=Y,20=N,21=N,22=N,23=N,24=N,
25=N,26=N,27=N,28=N,29=N,30=N,31=N,32=N
UPDN=N,ADDR=010,DBID=BC00D148
3
MIBA=H,MIBB=H,PORTS=2 ASRD=N
4
DACT=01
Status Displayed:
ISIB = Is the Intelligent Serial Interface Board installed?
ISIBs available for the AM2020/AFP1010 system include the SIB-2048A and
SIB-NET. For an AM2020/AFP1010 connected to a NOTI•FIRE•NET™
system however, the only ISIB that can be used is the SIB-NET. If a SIB-NET
is not installed, NOTI•FIRE•NET™ specific functions can not be pro-
grammed or read under Read Status (see Chapter One).
Due to its size, the Annunciator Read Status display is separated into two
screens, illustrated below. Pressing <ENTER> invokes the next display.
UPDN = Is the ACS Port upload/download enabled?
ADDR = FACP NOTI•FIRE•NET™ address.
*
DBID = Database identifier.
*
MIBA = MIB-W/WF threshold for Channel A. (On the MIB-WF, only
*
the Channel A threshold setting is used.)
MIBB = MIB-W threshold for Channel B.
*
PORTS = Number of data ports monitored.
*
ASRD=ACK/SIL/RES disabled at panel.
*
*
ASRE=ACK/SIL/RES re-enabled on LAN Fail
These items are NOTI•FIRE•NET™ specific functions and
*
are only displayed when a SIB-NET is installed.
DACT = Base address of the UDACT (blank for none installed).
NOTE
ASRE=N
2-13