This chapter covers the programming options of the AM2020/AFP1010 Combination Fire/Security Protective
Signaling System and the features available to the operator. This chapter is presented through the
perspective of the CRT-2 Monitor. The prompts are displayed on the CRT screen in the order that they appear
(top to bottom) on the pages that follow. For programming the control panel from the built-in keypad, an
overview of the panel's Display Interface Assembly (DIA-2020 or DIA-1010) is illustrated in Chapter Two,
Operation. Installation information for the CRT is located in Chapter 1.

Menus

At the top of each sub-menu in this programming guide, a string of keys are displayed to illustrate the
sequence of keys needed to reach a particular menu. For example:
D } X


Passwords

Access to keypad or menu levels one and two require entry of specific passwords. These levels allow an
authorized programmer to initialize or alter the programming of the AM2020/AFP1010. Level One and Level
Two entry requirements are defined as follows:
If the main operator of the system requires access to a function which is password protected, contact the
distributor who installed the system for the required password(s). The AM2020 and AFP1010 are shipped with
initial Level One and Level Two passwords of five zeroes (00000).

Backspace key

The Backspace key serves several purposes. At a menu prompt, the Backspace key aborts the selection of
that option:
ENTER@40@CHARACTER@USER@LABEL:
When entering data, the Backspace key erases the last character or digit entered:
ENTER@40@CHARACTER@USER@LABEL:@NOTIFIER
At certain points during operator or programming functions, the Backspace key aborts all the data just entered.
For instance, during Full Point Programming, a particular point must be fully programmed before the control
panel can use the information. If the Backspace key is pressed at a prompt ( : ) before all parameters (i.e.
address, Type ID, equation, etc.) for that point are entered into the control panel, then all previous entries for that
point will be ignored.

About Transponder Rapid All-Call

When the All Call button is pressed on an AMG connected to an AM2020/AFP1010 panel, an All Call activation
signal is received by the panel. Upon receipt of the All Call signal, the AM2020/AFP1010 panel will
immediately activate all specially programmed XP Transponder "SPKR" (programmed Software Type ID) circuits.
Programming is performed in the XP Transponder using the XRAM-1 (see XP Transponder System Manual).
Programming 15088:J 10/22/99
www.PDF-Zoo.com
Select Programming Mode
Alter Status
Programming
Unacknowledged points must be acknowledged prior to being reprogrammed.
V
1 X
OR
Select Partial Point
Programming
Level One password required.
Level Two password required.
NOTE
7 X
Select MESSAGE option to
change Custom User Label.