Table A-2 (Continued)
Type of Circuit
LIB-200 SLC Loop
A circuit or path directly
over which multiple
signals are transmitted
and received.
LIB-200A or LIB-400
SLC Loop
A circuit or path directly
over which multiple
signals are transmitted
and received.
NOTI•FIRE•NET™
SLC
A series of modules and
products which allow a
group of Fire Alarm
Control Panels (FACPs)
and other control
equipment to connect,
forming a true peer-to-
peer network
Appendices
15088:J
www.PDF-Zoo.com
Devices/Ratings
LIB-200 Board: Employs intelligent
detectors and addressable modules -
SDX-551,SDX-551TH,SDX-751, FDX-
551,CPX-551,CPX-751,IPX-751,MMX--
1, MMX-2, MMX-101,XP5-M, XP5-C,
CMX-1, CMX-2, NBG-12LX, BGX-10L,
XPP-1, ISO-X.Ten SLC Loops max per
AM2020 system,4 per AFP1010.
When more than 100 Isolator
Modules/Isolator Bases are connected
to an SLC Loop, decrease the 198
address capacity by two addresses for
every isolator in excess of 100.
LIB-200A/LIB-400 Board: Employs 99
intelligent detectors and 99
addressable modules - SDX-551, SDX-
551TH, SDX-751, FDX-551, CPX-551,
CPX-751, IPX-751, MMX-1, MMX-2,
MMX-101, XP5-M, XP5-C, CMX-1,
CMX-2, NBG-12LX, BGX-10L, XPP-1,
ISO-X. Ten SLC Loops max per
AM2020 system, four per AFP1010.
When more than 100 Isolator
Modules/Isolator Bases are connected
to an SLC Loop, decrease the 198
address capacity by two addresses for
every isolator in excess of 100.
MIB-W: Media Interface Board used to
connect nodes with twisted-pair wire
MIB-F: Media Interface Board used to
connect nodes with fiber-optic cable
MIB-WF: Media Interface Board used
to connect from twisted-pair wire to fiber
or fiber to twisted-pair wire at any
network node.
RPT-W: Repeater used to boost the
data signal between network nodes
supporting twisted-pair wire only.
RPT-F: Repeater used to boost the
data signal between network nodes
supportingh fiber-optic cable
RPT-WF: Repeater used to boost the
data signal between network nodes
supporting both twisted-pair wire and
fiber-optic cable
NAM-232W: Network Adapter Module
functioning as an interface between the
AFP200 FACP and the NOTI•FIRE•NET
with twisted-pair wire
NAM232F: Network Adapter Module
functioning as an interface between the
AFP200 FACP and the NOTI•FIRE•NET
with fiber-optic cable
10/22/99
Circuit Ratings
24 Volts DC nominal, 27.6 volts DC maximum.
Maximum length is 10,000 ft. (3048 m) per
channel (NFPA Style 4) or 10,000 ft. (3048 m)
total twisted-shielded pair length (NFPA Style 6
and 7). Maximum loop current is 200mA (short
circuit) or 100 mA (normal). Maximum loop
resistance is 40 ohms. Supervised and power-
limited.
24 Volts DC nominal, 27.6 volts DC maximum.
Maximum length is 12,500 ft. (3810 m) per
channel (NFPA Style 4) or 12,500 ft. (3810 m)
total twisted pair length (NFPA Style 6 and 7).
Maximum loop current is 200mA (short circuit) or
100 mA (normal). Maximum loop resistance is
50 ohms. Supervised and power-limited.
NFPA Style 4 (Class B). 312.5 Kbaud
transmission rate. Refer to the NOTI•FIRE•NET
Manual, Document 50257 for distance limits.
NFPA Style 4 (Class B). Fiber Type: 62.5/125
micrometers. Wavelength: 820 nanometers.
Maximum Attenuation: 10 dB. 312.5 Kbaud
transmission rate
NFPA Style 4 (Class B). 312.5 Kbaud
transmission rate. Port A - refer to the
NOTI•FIRE•NET manual, Document 50257 for
distance limits. Port B - Fiber Type: 62.5/125
micrometers, Wavelength: 820 nanometers,
Maximum Attenuation: 10 dB.
NFPA Style 4 (Class B). 312.5 Kbaud
transmission rate. Refer to the NOTI•FIRE•NET
Manual, Document 50257 for distance limits.
NFPA Style 4 (Class B). Fiber Type: 62.5/125
micrometers. Wavelength: 820 nanometers.
Maximum Attenuation: 10 dB. 312.5 Kbaud
transmission rate
NFPA Style 4 (Class B). 312.5 Kbaud
transmission rate. Port A - refer to the
NOTI•FIRE•NET manual, Document 50257 for
distance limits. Port B - Fiber Type: 62.5/125
micrometers, Wavelength: 820 nanometers,
Maximum Attenuation: 10 dB.
NFPA Style 4 (Class B). 312.5 Kbaud
transmission rate. Refer to the NOTI•FIRE•NET
Manual, Document 50257 for distance limits.
NFPA Style 4 (Class B). Fiber Type: 62.5/125
micrometers. Wavelength: 820 nanometers.
Maximum Attenuation: 10 dB. 312.5 Kbaud
transmission rate
Connections
NFPA Style 4: LIB-200
Channel A - Term. 1 (+), 3 (-);
Channel B - Term. 5 (+), 7 (-).
NFPA Style 6, 7: LIB-200
Term. 1, 5 (+); 3,7 (-).
NFPA Style 4: LIB-200A/LIB-
400
Channel A - Term. 1 (+), 3 (-);
Channel B - Term. 5 (+), 7 (-).
NFPA Style 6, 7: LIB-200A/LIB-
400
Term. 1, 5 (+); 3,7 (-).
Port A - TB1 - 1 and 2
Port B - TB1 - 3 and 4
Port A - U1 (Tx), U5 (Rx)
Port B - U2 (Tx), U3 (Rx)
Port A (wire) - TB1 - 1 and 2
Port B (fiber) - U2 (Tx), U3 (Rx)
Port A: TB1- 1 and 2
Port B: TB1- 3 and 4
Port A: U14 (Tx), U11 (RX)
Port B: U15 (Tx), U12 (RX)
Port A (wire) TB1- 1 and 2
Port B (fiber) U15 (Tx), U12
(RX)
PortA: TB2 - 1 and 2
Port B: TB2 - 3 and 4
Port A: J2 (Tx), J1 (RX)
Port B: J4 (Tx), J3 (RX)
A-7