Refer to Figure 1.3-16 for the wiring of security notification appliances (supplementary use only in UL listed
systems). See Table 1.1-1 in the introduction to this section for monitor and control module options.
Security 15088:J
10/22/99
www.PDF-Zoo.com
TENANT A
*
MM CM
SLC Loop
Configured as a Notification Appliance
Circuit (do not break tabs) and pro-
- +
grammed in the Protected Premises Unit.
Listed 24 VDC
Power Supply.
Figure 1.3-16 System Requirements
Motion Detector
Contact Switch
Contact Switch w/MM
RKS-S Remote Keyswitch w/MM
Notification Appliance w/CM
MM Security Area Monitor
ACM-16AT or ACM-32A Remote Annunciator
MM CM
Group Interface
Pull Station
Smoke Detector
SLC
AM2020/AFP1010
CMX-1
or
CMX-2
+24 VDC listed
Security Notification Appliance
CMX-1 or CMX-2
(activated polarity shown)
NOTE
The CMX may also control audio
speakers in an audio application. In
such
an
installation,
fire
conditions must have priority over
security conditions in the AMG-1 (refer
to the Voice Alarm Multiplex Manual).
Key
*
*
Group Interface must be
physically located in either the
protected premises or the
Central Station
Central Station
47K
End-of-Line Resistor
(A2143-00)
alarm
4-29