Smoke Detector Activation During Walk Test - Notifier AM2020 User Manual

Fire alarm control panel
Hide thumbs Also See for AM2020:
Table of Contents

Advertisement

Smoke Detector Activation During Walk Test

Activation of smoke detectors during Walk Test for the Series 500 smoke detectors can be accomplished by
placing the optional Test Magnet (System Sensor model number M02-24) against the cover opposite the test
module socket, as shown below:
The LEDs should track within 10 seconds indicating alarm and annunciating the panel. (The LEDs will turn off
when the magnet is removed.) If Alarm Verification is enabled for the detector, the magnet will have to be held in
place for a longer time until the system verification is completed.
The Series 700 smoke detectors can be activated during Walk Test by placing the Test Magnet against the cover
between LED 1 and the test module socket in the area shown below:
The LEDs should track within 30 seconds, indicating an alarm and annunciating the panel. (The LEDs will turn off
when the magnet is removed.)
Programming 15088:J 10/22/99