Design Considerations; Wiring Selection Chart; Appendix Acircuit/Device Ratings - Notifier AM2020 User Manual

Fire alarm control panel
Hide thumbs Also See for AM2020:
Table of Contents

Advertisement

G
ENERAL
Appendix A outlines the various circuits and devices that can be employed with the AM2020/AFP1010.
S
A.1 D
ECTION
Each of the various types of circuits within an AM2020/AFP1010 Fire Alarm Control System has a specific
type of wire that must be used in order to ensure proper operation. In addition, the wire gauge of a particular
circuit is contingent on the length of that circuit. To determine the specific wiring requirements for each circuit,
refer to Table A-1.
• If the SLC Loop is to be run in conduit with Notification Appliance Circuits, the risk of encountering problems can be
greatly reduced by using the LIB-200A or LIB-400 or exclusively employing electronic sounders instead of more elec-
tronically noisy notification appliances such as electromechanical bells or horns.
• In order to comply with the Federal Communications Commission (FCC) regulations on electrical energy
radiation when using the LIB-200, any wire entering or exiting the AM2020/AFP1010 cabinet that is not in
conduit must be of the twisted-shielded type. For termination of the LIB-200 SLC Loop shield, refer to the
Installation section of the manual originally supplied with the LIB-200.
Circuit
Type
LIB-200
SLC loop
LIB-200A or
LIB-400
SLC loop
EIA-485
EIA-232
MMX
XPM-8
CMX
XPC-8
Power Runs
Power Runs
Appendices
15088:J
www.PDF-Zoo.com
CIRCUIT/DEVICE RATINGS
C
ESIGN
ONSIDERATIONS
Circuit Functions
Wire Requirements
Twisted-shielded pair, 12 to 18 AWG
Connects to Intelligent
(3.25 to 0.75 mm²). 40 ohms max
Detectors and
per length of Style 6 and 7 loops. 40
Addressable Modules,
ohms per branch max for Style 4
and to XP Transponders
loops.
Connects to Intelligent
Twisted unshielded pair, 12 to 18
Detectors and
AWG (3.25 to 0.75 mm²). 50 ohms
Addressable Modules,
max per length of Style 6 and 7
to XP Transponders,
loops. 50 ohms per branch max for
and XP5 Transponders
Style 4 loops
Connects to LCD-80,
Twisted-shielded pair with a
AMG-1 and to
characteristic impedance of
Annunciator Control
approximately 120 ohms.
System Modules
18 AWG (0.75 mm²) minimum.
Connects to CRTs and
Twisted-shielded pair.
remote printers
18 AWG (0.75 mm²) minimum.
12 to 18 AWG(3.25 to 0.75 mm²).
Maximum loop wire resistance is 20
Initiating Device Circuit
ohms (MMX-1, MMX-101) or 100
ohms (XPM-8).
12 to 18 AWG (3.25 to 0.75 mm²).
Notification Appliance
MPS-24A: At alarm current level, no
Circuit
more than a 1.2 volt drop at the end
of the circuit.
12 to 18 AWG (3.25 to 0.75 mm²).
To CMXs, XPC-8s, and
Size wire so that no more than 1.2
XP5-Cs
volt drop across wire run from supply
source to end of any branch.
12 to 18 AWG (3.25 to 0.75 mm²).
Size wire so that no more than 2.4
To annunciators
volts drop across wire run from
supply source to end of any branch.
Table A-1 Wiring Selection Chart
10/22/99
APPENDIX A
NOTES
Distance
(feet/meters)
10,000/3048
8,000/2438
4,875/1485.9
3,225/982.98
12,500/3810
9,500/2895.6
6,000/1828.8
3,700/1127.76
6,000/1828.8
6,000/1828.8
6,000/1828.8
4,000/1219.2
See EIA-232D
Standard
5,000/1524
4,000/1219.2
2,438/743.1
1,613/491.64
Installer
Calculations
Required
Installer
Calculations
Required
Installer
Calculations
Required
Typical Wire Type
Belden 9583, West Penn 999, Belden B5020FL
(12 AWG/3.25 mm
2
)
Belden 9581, West Penn 995 (14 AWG/2.00 mm
Belden 9575, West Penn 991 (16 AWG/1.30 mm
Belden 9574, West Penn 975 (18 AWG/0.75 mm
Belden 9582, West Penn 998 (12 AWG/3.25 mm
Belden 9580, West Penn 994 (14 AWG/2.00 mm
Belden 9572, West Penn 990 (16 AWG/1.30 mm
Belden 9571, West Penn 980 (18 AWG/0.75 mm
Belden 9583, West Penn 999, Belden B5020FL
2
(12 AWG/3.25 mm
)
Belden 9581, West Penn 995 (14 AWG/2.00 mm
Belden 9575, West Penn 991 (16 AWG/1.30 mm
Belden 9574, West Penn 975 (18 AWG/0.75 mm
Belden 9583, West Penn 999 Belden B5020FL
(12 AWG/3.25 mm
2
)
Belden 9581, West Penn 995 (14 AWG/2.00 mm
Belden 9575, West Penn 991 (16 AWG/1.30 mm
Belden 9574, West Penn 975 (18 AWG/0.75 mm
Belden 9583, West Penn 999, Belden B5020FL
(12 AWG/3.25 mm
2
)
Belden 9581, West Penn 995 (14 AWG/2.00 mm
Belden 9575, West Penn 991 (16 AWG/1.30 mm
Belden 9574, West Penn 975 (18 AWG/0.75 mm
Belden 9583, West Penn 999, Belden B5020FL
2
(12 AWG/3.25 mm
)
Belden 9581, West Penn 995 (14 AWG/2.00 mm
Belden 9575, West Penn 991 (16 AWG/1.30 mm
Belden 9574, West Penn 975 (18 AWG/0.75 mm
Belden 9583, West Penn 999, Belden B5020FL
2
(12 AWG/3.25 mm
)
Belden 9581, West Penn 995 (14 AWG/2.00 mm
Belden 9575, West Penn 991 (16 AWG/1.30 mm
Belden 9574, West Penn 975 (18 AWG/0.75 mm
Belden 9583, West Penn 999, Belden B5020FL
2
(12 AWG/3.25 mm
)
Belden 9581, West Penn 995 (14 AWG/2.00 mm
Belden 9575, West Penn 991 (16 AWG/1.30 mm
Belden 9574, West Penn 975 (18 AWG/0.75 mm
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
A-3