The equipment or material acceptable for use in accordance with the Report of Materials and Equipment Accep-
tance (MEA) Division be accepted under the following conditions:
a. When used with central office communicator or transmitter, the installation and operation of the equipment
and devices listed herein shall comply with Fire Department rule #3-RCNY 17-01, NFPA 72, and shall have
the capability of transmitting separate and distinct signals to indicate manual pull station alarm, sprinkler
waterflow alarm, supervisory signal indications and trouble indications.
b. LCD-80TM which can be remotely located up to 3000 feet from the control panel has a remote acknowl-
edge, silence, and reset features which can affect the control panel from remote locations. These features
are not to be employed in any installation in New York City.
c. Smoke Control station and expander (SCS-8 and SCE-8) are to be used in conjunction only with Notifier models
AM2020/AFP1010 fire alarm control panels when configured for smoke control. The SCS-8 must be mounted in
a separately listed model CAB-3 or ABS-4D enclosure which provides mounting for the SCS-8 and limited
access to the manual override switches. These smoke controls shall be arranged such that controls may only be
operated by use of or given access to by means of a fire department '1620' key.
d. AM2020/AFP1010 control panels shall provide either redundant processors or Class A redundant SLC
loops as needed to positively assure the fail safe control of door locks, ventilation fans, elevator recall and
evacuation signalling which will not be rendered inoperable in the event of a fire alarm condition when
installed in any building which is required by code to have a Fire Command Station.
f.
HVAC systems shall not be arranged to automatically restart upon the reset of a smoke detector or
control board.
g. The AM2020/AFP1010 is intended to be used as a Central Station Protected Premise Unit, it is to be
connected to a listed Ademco Model 678UL-F which in turn is connected to a Listed Ademco Model 685
receiver.
h. To provide service as a central station protected premises unit utilizing digital alarm communication tech-
niques, the AM2020/AFP1010/ control unit is intended to be interconnected to a Listed FireLite Model Notifier
911C/911AC digital alarm communicator transmitter or employ the listed FireLite Model Notifier 911/911A
subassembly.
i.
The control units (AM2020/AFP1010/) may also be connected to the separately listed model UDACT to
provide remote station or central station service.
j.
When the AM2020 control panel is intended for use as a proprietary receiving unit, the system must utilize
the CRT-1 terminal keyboard and Models P-80, PRN-2, PRN-3, or PRN-4 printers as the operators terminal
station. Both the CRT-1 and Model P-80, PRN-2, PRN-3, or PRN-4 must be located next to the AM2020
control unit.
k. The LCD-80TM remote annunciator shall only be used with the AM2020, AFP1010, and AFP-200 control
units.
All shipments and deliveries of such equipment shall be provided with a metal tag suitably placed, certifying
that the equipment shipped or delivered is equivalent to that tested and accepted for use, as provided for in
Section 27-131 of the Building Code.