Figure 1.3-10 Programming Key (continued):
NIB-96
NIB-96 Network Interface Board (continued)
Protected Premises Unit (Slave)
Central Station RIngback
**Indicates installer-specified NIB point.
Security 15088:J
10/22/99
www.PDF-Zoo.com
Arming Switch
Annunciator Point: AssPl**
Type ID: AMON
Annunciator Point: AssPm**
Type ID: ACON
Tamper Switch
Annunciator Point: AssPn**
Type ID: AMON
Central Station (Master)
Point
Monitor Module Point (PPU Arming Switch)
l**
Address: LXXMYY
Type ID: SACM
Control-By-Event: (Zc) Unique Zone Number
Custom Label: Installer Specified.
Tracking: Yes
Walk Test: No
Annunciator: Yes - Provides visual
Annunciator Point: AXXPYY (if used).
Control Module Point (Ringback)
m**
Address: LXXMYY
Type ID: CMXS
Control-By-Event: (Zc) (Same as Point I)
Custom Label: Installer Specified.
Signal Silence: No
Walk Test: No
Annunciator: No (Not required).
Monitor Module Point (PPU Tamper Switch)
n**
Address: LXXMYY
Type ID: SSYM
Control-By-Event: (Installer Specified)
Custom Label: Installer Specified.
Tracking: Yes - Security tamper
Annunciator: No (Not required).
indication of Protected Pre-
mises Arm/Disarm status at
the Central Station.
No - does not provide visual
indication of Protected Pre-
mises Arm/Disarm status.
conditions will restore auto-
matically at the Central Sta-
tion after restoral at the Pro-
tected Premises.
No - Security tamper condi-
tions will latch in the Central
Station until reset at the Cen-
tral Station - short condition
only.
4-23