Plug this DB-25 connector into the
EIA-232 Port of the printer.
• Outputs are power limited and are not supervised.
• Connections must be made with overall foil/braided-shield twisted paired cable suitable for EIA-232 applications.
• The SIB can employ two printers.
• Set the DIP switches as follows:
Installation 15088: J 10/22/99
www.PDF-Zoo.com
Keltron Printer
Model VS4095/5
nc
4
Main Power Supply
TB3- 3 (+)
MPS-24A:
and
TB3-4 (-)
SP1-1
OFF
SP1-2
ON
SP1-3
OFF
SP1-4
ON
SP1-5
OFF
SP1-6
ON
SP1-7
ON
SP1-8
OFF
50 feet (15.24 meters)
maximum
(typical)
Wiring distance limited by
cable capacitance.
EIA-232E standard.
Twisted Pair
Twisted Pair
Power-limited
NOTES
SP2-1
OFF
SP2-2
OFF
SP2-3
OFF
SP2-4
OFF
SP2-5
OFF
SP2-6
OFF
SP2-7
ON
SP2-8
OFF
SIB-2048A
or
SIB-NET
See
SIB Connector P3
(Power-limited)
EIA-232 Reference
5
Transmit to Printer
6
EIA-232 Reference
7
Ready/Busy
8
from Printer
DC IN -
+ DC IN
Keltron Remote Printer
Model VS4095/5