Figure 1.3-10 Programming Key (continued):
8. Zone Active 1.5 Min. After Arming System
Type ID: RZON
Control-By-Event: DEL(00.01.30 (Zab*))
Custom Label: Installer Specified.
Annunciator: No (Not required).
9.
Zone Providing 30 Sec. Entry/Exit Delay (En-
try/Exit Door Only) When System Is Armed
Type ID: RZON
Control-By-Event:
OR(AND(Zab* Zag* Zae*) AND(Zab* Zaf*))
Ç
causes Zone Zah* to
activate if entry/exit
time is exceeded.
Custom Label: Installer Specified.
Annunciator: No (Not required).

Notification Appliance w/CM Control Module

When using an optional Control Module for Notification Appliances intended to indicate a security violation, this
CM may be programmed with the following Control-By-Event equation:
resulting in 15 minutes of Notification Appliance activation after a security violation.
*Zaa through Zal are each unique installer-specified zone numbers. Zaa is the lowest specified zone number (high-
est priority) and Zal is the highest specified zone number (lowest priority).
Example:
Security 15088:J
10/22/99
www.PDF-Zoo.com
Zone: Zag*
Zone: Zah*
ÈÇ
causes
Zah* to activate
if entry/exit door
is left open.
AND(Zab* SDEL(00.00.00 00.15.00 (Zaj*)))
Zaa
Zab
Zac
Z5
Z12
Z22
ï
ï
ð
For-
ward
Zones
Zone Boundary greater than or equal to Z22 and less than Z180.
10. Zone Active for a Minimum of 30 Sec. if Entry/
Exit Delay Is Violated (Entry/Exit Door Only)
When System Is Armed
Control-By-Event:
AND(Zab* SDEL(00.00.00 00.00.30 (Zah*)))
Custom Label: Installer Specified.
Annunciator: No (Not Required).
11. Zone Active at Least 30 Sec. for Any Security
Breach While System Is Armed
È
Control-By-Event: OR(Zad* Zah* Zai*)
Zone
Custom Label: Installer Specified.
Annunciator: No (Not required).
12. Zone which remains Active until Reset when
security violation occurs and the System is
Armed.
Control-By-Event: SDEL(00.00.00 (Zaj*))
Custom Label: Installer Specified.
Annunciator: Yes
Annunciator Point: ArrP2
13. Zone Active when Tamper Switch Is Active
Control-By-Event: ( )
Custom Label: Installer Specified.
Annunciator: Yes
Annunciator Point: ArrP5
Zad
Zae
Zaf
Zag
Z180
Z188
Z199
Z200
Reverse
Zones
Zone: Zai*
Type ID: RZON
Zone: Zaj*
Type ID: RZON
Zone: Zak*
Type ID: RZON
Zone: Zal*
Type ID: RZON
Zah
Zai
Zaj
Z210
Z211
Z212
ð
Zak
Zal
Z216
Z218
4-25