Programming for Dual Stage Alert/Evacuation operation (for use in Canada only)
An XPC-8 Notification Appliance Circuit module can be configured for Dual Stage Alert/Evacuation operation.
Under this mode of operation each circuit operates in one of two stages: alert or evacuation. When configured
this way, each notification appliance circuit has two addresses associated with it. Refer to the XP Series
Transponder Manual for additional information.
The first address is the control address. Activating this point (through its Control-By-Event programming) will
turn the notification appliance circuit on. This point uses the Software Type ID CON.
The second address is the stage selection address. This point decides what state an active notification
appliance circuit will be in. Activating this point will put the notification appliance circuit into evacuation mode.
If this point is not activated the circuit will be in alert mode. This point uses the Software Type ID FORC.
NOTE
If an unacknowledged circuit is in alert mode for more than five minutes, all activated circuits on the
XPC-8 will change to the evacuation pulse rate.