Point Read

Selecting 2 from the Read Status Menu allows the operator to review the various detector, module, software
zone or annunciator point parameters entered into the system. The system prompts the operator for the
address of the point to be read:
Upon entering the address, the system will display a distinct screen format, depending on the particular type
of device being read, as illustrated below:
After a one-minute timeout, the Control-By-Event (CBE) and the annunciator point mapped address
is displayed for devices and zones. Cooperative Control-By-Event (CCBE) is displayed for reverse
zones and are only used as part of the NOTI•FIRE•NET™ operation. To display this information
Status: DISABL, ALARM:, TROUBL, NORMAL.
Device
Disabled
Device in
Alarm
Day/Night Detector Sensitivity Setting:
Low, Medium, High.

Detector Verification

If verification is enabled for this point, the V indicator appears and the 3-digit counter shows the number of times
the verification timer was activated for the point without going into alarm . The counter returns to zero when power
is cycled to the AM2020/AFP1010 or by following the procedure in the Resetting Sensor Verification Counters
section of this document. If you disable verification, the counter will retain its last value. If verification is not
enabled for this point, the V indicator does not appear; however, the 3-digit number still appears. Note that the
counter does not increment unless verification is enabled.
A detector may be in periodic test during a read status. In this case, the detector status will be
normal but the percentage of alarm threshold will be greater than 100%. If this happens, wait one
2-14
www.PDF-Zoo.com
ENTER@LXX(D/M)YY,@ZXXX@OR@AXXPYY@FOR@PT.
@STATUS (BCKSPC TO ABORT)
immediately, press ENTER after the status line appears.
Software Type I.D.20-Character Custom Label
NORMAL@SMOKE(ION)@@@@COMPUTER@ROOM@SMOKE
@D@@@A@T@K@@@@@@@SH@V000@H@034@@@@@L02D26
Tracking
Selected
Device in
Trouble
minute, then perform another read status.
NOTE

Detectors

Verification
Percentage of
Counter
Alarm Threshold
Sensitivity Selection:
Low, Medium, High.
NOTE
READ STATUS
Menu Option 2
@@@@:
Address
Operating 15088: J 10/22/99