While a fire alarm system may lower insurance Fire Alarm System Limitations rates, it is not a substitute for fire insurance! An automatic fire alarm system–typically made up of smoke Heat detectors do not sense particles of combustion and detectors, heat detectors, manual pull stations, audible warn- alarm only when heat on their sensors increases at a prede- ing devices, and a fire alarm control with remote notification termined rate or reaches a predetermined level.
Installation Precautions Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be con- Like all solid state electronic devices, this system may nected to the fire alarm control panel. Disconnect all sources operate erratically or can be damaged when subjected to light- of power before servicing.
Page 10
NONRESET CTL Phone Standard telephone circuit TELEPHONE NAC, short = normal; supervised for open circuits and ground faults. Always INSTANT RELE non-silenceable and switch-inhibited. Table 12 Control Module (CMX) Type Codes AFP-300/AFP-400 Programming PN 50259:D 04/17/01 Technical Manuals Online! - http://www.tech-man.com...
Page 11
Supervised NAC (MPS-400 only) REL CODE BELL NAC, short = normal; supervised for open INSTANT RELE circuits and ground faults. Always non-silenceable and switch-inhibited. Table 13 NAC/Panel Output Circuit Type Codes AFP-300/AFP-400 Programming PN 50259:D 04/17/01 Technical Manuals Online! - http://www.tech-man.com...
Page 12
For example, press then press <7> to enter a “=” character. /2:(5 &$6( & Save the new message Press Table 15 Changing System Message AFP-300/AFP-400 Programming PN 50259:D 04/17/01 Technical Manuals Online! - http://www.tech-man.com...
Page 14
Each detector provides a host of selectable intelligent options. You can program $ODUP 6HQVLWLYLW\ Pre-Alarm and Alarm detector sensitivity levels (Table 38) in the widest allowed ranges (0.03 to 4% per foot obscuration). The AFP-300/AFP-400 provides nine levels of Pre-Alarm (PA:1–PA:9) and Alarm (AL:1–AL:9) in percent per foot obscuration: 3$ •...
Page 15
3. Suitable for open area protection only with 0 to 300 feet per minute air velocity. 4. Use only Alarm sensitivity setting of AL=1, AL=2 or AL=3 for Ion detectors installed in Canada. Table 38 Detector Sensitivity (in percent per foot obscuration) AFP-300/AFP-400 Programming PN 50259:D 04/17/01 Technical Manuals Online! - http://www.tech-man.com...
Page 16
Record all events for each tested detector with an electronic history file or a printout. At the end of the 90 day test: An authorized Notifier representative, or an end user trained by an authorized Notifier representative must inspect the results of the test.
Page 17
Activation can Multisensor smoke detector (IPX series) and MULTISENSOR perform CBE Acclimate™ (FAPT series) Activation can Heat detector (FST, FDX series) HEAT ANALOG perform CBE Table 9a Intelligent Detector Type Codes AFP-300/AFP-400 Programming PN 50259:D 04/17/01 Technical Manuals Online! - http://www.tech-man.com...
Need help?