3=PPRG
Option 3 from the Programming Menu allows the programmer to change the operational parameters of SLC Loop
devices, software-defined zones, and annunciator points.
After selecting option 3 from the Main Programming menu, the display will show the Partial Point Programming
submenu:
PRESS@1=TYPID,2=CBE,3=LBL,4=OPTNS,5=AMAP,6=CCBE@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@:
The Partial Point Programming submenu has six options, where:
1=TYPID
2=CBE
3=LBL
4=OPTNS
5=AMAP
6=CCBE
The Partial Point Programming flow chart is located in Figure 1-10. Detailed information on the Partial Point
Programming options follows.
Each option under Partial Point Programming prompts the programmer to enter the address of the
detector, module, zone, or annunciator point to be affected. Leading zeros are not required. The
LXX(D/M)YY (for devices) or
SLC Loop
1 to 10 (AM2020),
1 to 4 (AFP1010)
3-30
www.PDF-Zoo.com
Type ID - Changing the Software Type ID of SLC Loop devices, zones and annunciator
points.
Control-By-Event - Redefining the Control-By-Event associated with each detector,
module, or zone.
Label - Renaming the custom user label for any detector, module, or zone.
Options - Selecting the optional features associated with any detector or module.
Annunciator Point Mapping - Selecting Annunciator Point Mapping for any detector,
module, or zone.
Cooperative Control-By-Event - Edit the CCBE associated with reverse activated
zones for NOTI•FIRE•NET.
address assumes the following format:
ZXXX (for zones) or AXXPYY (for annunciator points)
Addressable Detector or Mod-
ule followed by an address in
the range 1 to 99
Example: For the 44th module on SLC Loop 3, enter L3M44
D }X3X
NOTE
Software-defined
Annunciator
Zone Z1 to Z240
Module 1 to 32
Annunciator
Point 1 to 64
Programming 15088:J 10/22/99