About SIB-NET

The SIB-2048A and SIB-NET serial communications boards are available for use on the AM2020/AFP1010
system (see Chapter One). For the AM2020/AFP1010 with NOTI•FIRE•NET™ system, only the SIB-NET may
be used. If a SIB-NET board is not installed, specific NOTI•FIRE•NET functions can not be programmed or
viewed under Read Status.
When a Network Reporting Terminal (NRT) is present on the NOTI•FIRE•NET, programming and
read status operations should always be performed from the NRT . If an INA is present on the
NOTI•FIRE•NET and no NRT is employed, programming and read status operations should be
performed from the INA. Never attempt to perform programming or read status operations from the
local panel when the same operations are being performed from the NRT or INA. For more information
on performing read status operations on the NRT or INA, refer to the NRT manual, Document 15090
When changing system programming on NOTI•FIRE•NET, it may be necessary to power down the
3-4
www.PDF-Zoo.com
NOTES
and the INA manual, Document 15092.
control panel to synchronize the network.
Programming 15088:J 10/22/99